Grid integration, ancillary services, and regulation
How much solar PV and battery storage a power system can take, which integration measures cost least, and how regulation and markets can make them happen.
As the share of solar PV grows, system operators have to manage voltage, frequency, reserves, and forecast errors in new ways, and regulators have to decide who provides these services and who pays for them. My work connects the engineering to the economics and the rules: what limits PV in a given network, which measures address it, what each one costs, and how the regulatory framework can put them in place.
What I have worked on
- What limits PV, and what can be done about it. A two-part review of how high PV penetration affects voltage, frequency, protection, harmonics, rotor angle stability, and flexibility requirements, with the penetration limits reported in the literature and the tools needed to check them. The second part assesses the solutions (forecasting, voltage and frequency regulation, harmonic compensation, reactive power management, generator planning and dispatch, and adaptive protection), what limits their implementation, and who bears their cost. They are my most cited papers.
- The cost of integrating PV. I proposed a levelised cost of PV integration: the capital and operating cost of an integration measure divided by the PV energy generated over its lifetime. On 69-bus and 119-bus distribution networks with real weather and price data, combined active and reactive power control was the most cost-effective way to mitigate overvoltage, followed closely by reactive power control and curtailment. Battery storage would need to become more than 80% cheaper to be viable for overvoltage mitigation alone.
- Reactive power from PV inverters. My PhD at the National University of Singapore (NUS) priced the reactive power that PV inverters can supply to the grid, including the cost of the extra wear on the inverter. Lifetime reduction made up more than half of that cost at low PV penetration, and less at high penetration, when the support is spread over more systems. The work identified the range of incentives that would make the service worthwhile for PV owners, and local control methods that perform almost as well as centralised optimisation without any communication between inverters.
- Behind-the-meter storage that operators cannot see. Batteries that are netted out with customer load and not dispatched by the operator increased ramping requirements, made net demand and prices more volatile, and raised system operating cost on a standard test system. Operators should assess this effect in their own networks before such storage becomes widespread.
Where I have applied it
- Singapore, 2019 to 2022. I led the PV grid integration working group of a national solar forecasting programme for the Energy Market Authority (EMA) and Singapore Power (SP). We modelled Singapore's networks, studied how distributed PV and storage affect capacity adequacy, grid stability, reserve requirements, generation mix, and prices, compared integration measures, and presented the findings to EMA and SP.
- Indonesia, since 2023. Through GIZ, I was one of three main authors, with Energynautics and UMBRA, of two studies for the Ministry of Energy and Mineral Resources (MEMR): a comparative study of ancillary services, which benchmarks reference markets including Singapore, and a regulatory framework and business model for battery energy storage systems (BESS), which compares ownership, contracting (hybrid power purchase agreements, capacity, and tolling agreements), procurement, and pricing. I have also worked with GIZ on rooftop PV hosting capacity and quotas, and trained PT PLN (Persero) staff on ancillary services and demand response.
Questions I help answer
- How much PV can this network host before voltage, frequency, or reserves become binding?
- Which measure (curtailment, inverter reactive power, batteries, or network reinforcement) solves a given problem at least cost?
- Which ancillary services should PV and batteries provide, and how should they be procured and paid for?
- How should regulation treat battery storage: who owns it, how it is contracted, and how it is paid?
Publications
- 2026Comparative Study of Ancillary Service as Recommendation for Ancillary Service Provision for IndonesiaGIZ Energy Programme Indonesia & ASEAN, in cooperation with the Directorate General of Electricity, Ministry of Energy and Mineral Resources (PDF)
- 2026BESS Regulatory Framework and Business ModelGIZ Energy Programme Indonesia & ASEAN, in cooperation with the Directorate General of New, Renewable Energy and Energy Conservation, Ministry of Energy and Mineral Resources (PDF)
- 2024The value of solar forecasts and the cost of their errors: A reviewRenewable and Sustainable Energy Reviews 189, 113915 · doi:10.1016/j.rser.2023.113915
- 2022Levelised cost of PV integration for distribution networksRenewable and Sustainable Energy Reviews 169, 112922 · doi:10.1016/j.rser.2022.112922
- 2022Effects of ‘invisible’ energy storage on power system operationsJournal of Energy Storage 45, 103626 · doi:10.1016/j.est.2021.103626
- 2020Review of power system impacts at high PV penetration Part I: Factors limiting PV penetrationSolar Energy 210, 181–201 · doi:10.1016/j.solener.2020.06.097
- 2020Review of power system impacts at high PV penetration Part II: Potential solutions and the way forwardSolar Energy 210, 202–221 · doi:10.1016/j.solener.2020.08.047
- 2020Local reactive power dispatch optimisation minimising global objectivesApplied Energy 262, 114529 · doi:10.1016/j.apenergy.2020.114529
- 2020Reactive Power Support Using Photovoltaic Systems: Techno-Economic Analysis and Implementation AlgorithmsSpringer Theses, Springer Nature · doi:10.1007/978-3-030-61251-1
- 2020Dynamic Economic Dispatch Scenario Planning for Power Grids with PVs and StorageIEEE International Women in Engineering (WIE) Conference on Electrical and Computer Engineering · doi:10.1109/WIECON-ECE52138.2020.9397968
- 2018Economic and technical analysis of reactive power provision from distributed energy resources in microgridsApplied Energy 210, 827–841 · doi:10.1016/j.apenergy.2017.08.154
- 2018Reactive power cost from PV inverters considering inverter lifetime assessmentIEEE Transactions on Sustainable Energy 10(2), 738–747 · doi:10.1109/TSTE.2018.2846544
All 20 publications on this topic